Biotec 5-7

The requirement for a more flexible plant has led to the development of the Biotec™ 5-7 – a whole new range of sewage treatment plant to meet the demands of today’s consumer.

Application

Klargester packaged sewage treatment systems are available in a range of sizes – from a 2 bedroomed house up to a population of 375.

This webpage covers the larger Biotec™ models which are used for developments from 40 to 85 people.

  • Small housing developments
  • Campsites and holiday park homes
  • Public houses
  • Hotels
  • Golf and leisure clubs
  • Office developments
  • Government and defence

For details of our small domestic Biotec™ models please click here

Features and Benefits

  • High rate performance across a range of influent and effluent qualities
  • Low head loss
  • Minimal footprint area
  • Single piece tank for rapid installation and reduced costs
  • Variable invert options
  • Minimal visual impact (below ground)
  • Low running costs
  • May be installed in trafficked areas (subject to loading)
  • Compliant with EN-12255
  • Designed for applications selected in compliance with British Water Code of Practice Flows and Loads
  • Low maintenance
  • Alarm protected

Process Design

The Biotec™ 5-7 range of sewage treatment plants employ a plug flow combination of aerobic processes in a fluidised bed arrangement. This operates in conjunction with an advanced system of air diffusers and selected media to deliver optimum levels of purification. This process takes place in three distinct stages:-

1. Primary Settlement
This is the initial stage of treatment and simply involves the retention of coarse solids present in raw sewage and wastewater for subsequent gradual breakdown. The Biotec™ 5-7 range features two chambers to ensure efficient operation with a flow balancing facility.

2. Biological Treatment
Substantial BOD reduction takes place here, where the carbonaceous pollutants are removed by presenting the sewage to the micro-organisms in the presence of oxygen. The treatment is achieved by high efficiency air diffusers continually pumping oxygen through the biological media and fluidised effluent. Biotec™ models utilise two aerobic treatment chambers for standard performance applications.

3. Settlement
A natural by-product of biological treatment is humus sludge and this is separated for further treatment. The treated effluent is discharged via the outlet. In standard configuration The Biotec™ 5-7 range will deliver a treatment better than 20mg/l BOD, 30mg/l S.S., with ammonia levels better than 20mg/l depending on the application.

Flow Management

The Biotec™ 5-7 range design incorporates flow management in order to both stabilise influent volume variations and to minimise hydraulic impact on the final settlement process. Such control ensures that final effluent remains at a consistently high quality.

Options

  • Choice of inverts (from 0.5 to 2.0m)
  • Standby blowers
  • Alarm systems
  • Sample chambers
  • Pumping stations
  • Extension shafts (to 2.0m maximum standard invert)

Service & Maintenance

Biotec's individual chambers have large dedicated manholes to allow quick and easy maintenance access. Servicing is also simplified as Biotec’s flow control makes it unnecessary to empty the biozones, as is the case with other designs of treatment plant.

As a result there is no loss of plant performance during periodic maintenance. The biozones immediately resume operation following servicing, whilst the influent level is restored.

Specification

Biotec™ 5

Biotec 5-6 Spec
Biotec™ Model 5 6
A Overall Length (m) 7.20 9.40
B Overall Width (m) 2.02
C Height (m)
500mm Inlet / 600mm Outlet Invert*
1000mm Inlet / 1100mm Outlet Invert*
1500mm Inlet / 1600mm Outlet Invert*
2000mm Inlet / 2100mm Outlet Invert*

2.25
2.75
3.25
3.75
D Diameter (m) 1.87
Volume (m2) 19 25
Weight approx (kg) 1200 1450
Inlet / Outlet Diameter (mm) 110
Maximum flow (m2/day) 8 11
Retention time (hrs) 51 47

Notes:
Extension necks can be added to turrets to achieve deeper inverts. Alternative pipe sizes may be ordered. For any deep installation above our standard 2m invert, we recommend independent civil engineer advice be sourced.

Weights are dry weights and installers must ensure there is no water in the tanks before lifting. All weights are approximate

Kingspan Environmental reserve the right to alter the above dimensions without prior notice.

Biotec™ 6-7

Biotec 6-7 Spec
Biotec™ Model 7
A Overall Length (m) 7.4
B Overall Width (m) 2.8
C Height (m)
500mm Inlet / 650mm Outlet Invert*
1000mm Inlet / 1150mm Outlet Invert*
1500mm Inlet / 1650mm Outlet Invert*
2000mm Inlet / 2150mm Outlet Invert*

3.0
3.5
4.0
4.5
D Diameter (m) 2.6
Volume (m2) 34
Weight approx (kg) 3000
Inlet / Outlet Diameter (mm) 160
Maximum flow (m2/day) 17
Retention time (hrs) 45

Notes:
Extension necks can be added to turrets to achieve deeper inverts. Alternative pipe sizes may be ordered. For any deep installation above our standard 2m invert, we recommend independent civil engineer advice be sourced.

Weights are dry weights and installers must ensure there is no water in the tanks before lifting. All weights are approximate

Kingspan Environmental reserve the right to alter the above dimensions without prior notice.

Biotec 5-7 Control Panel

Biotec™ 5-7 Control Panel

  • Weatherproof to IP66 rating, can be externally mounted
  • Fully pre-programmed treatment plant control with
    alarm/fault log
  • Automatic re-start from power failure condition
  • Integrated level protection
  • Visual and audible alarm indicators

Service & Maintenance

Biotec's individual chambers have large dedicated manholes to allow quick and easy maintenance access. Servicing is also simplified as Biotec’s flow control makes it unnecessary to empty the biozones, as is the case with other designs of treatment plant.

As a result there is no loss of plant performance during periodic maintenance. The biozones immediately resume operation following servicing, whilst the influent level is restored.

Specialist Advice

Delivering high quality effluent requires careful evaluation of the various parameters affecting each scheme. Relatively minor changes may result in the loss of one or more of the required effluent qualities.

Kingspan Environmental’s team of technical specialists assess each site’s demands and application and tailor a technical specification to meet the consent requirements. Plant sizing is not only calculated on current demand but also gauged on potential future loading in order to meet the latest legislative criteria and customer needs as appropriate.

Installation

Case study

A treatment plant serving a 3-bedroom farmhouse

The client approached Klargester to discuss the options for replacing a failing brick Septic Tank. Key criteria were to reduce frequency of tank-emptying visits and to use existing soakaway without the risk of blockage. Major concern was also to reduce pollution of surrounding streams and watercourses.

Contact us

Klargester
College Road North
Aston Clinton, Aylesbury
Buckinghamshire
HP22 5EW

Tel: 01296 633000
Fax: 01296 633001
info@klargester.com